IEC Electrical | 75 | 150 | 275 | 320 | 385 | 440 |
Nominal AC Voltage (50/60Hz) | Uo/ Un | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Maximum Continuous Operating Voltage (AC) | Uc | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Nominal Discharge Current (8/20 μs) | In | 40 kA | 40 kA | 40 kA | 40 kA | 40 kA | 40 kA |
Maximum Discharge Current (8/20 μs) | Imax | 80 kA | 80 kA | 80 kA | 80 kA | 80 kA | 80 kA |
Impulse Discharge Current (10/350 μs) | Iimp | 7kA |
Voltage Protection Level | Up | 0.8 kV | 1.2 kV | 2 kV | 2 kV | 2 kV | 2.2 kV |
Response Time | tA | < 25 ns |
Back-Up Fuse (max) | 125 A gL / gG |
Short-Circuit Current Rating (AC) | lSCCR | 35 kA / 50 kA |
TOV Withstand 5s | UT | 90V | 180V | 335V | 335V | 335V | 580V |
TOV 120min | UT | 115V | 230V | 440V | 440V | 440V | 765V |
| mode | Withstand | Withstand | Safe Fail | Safe Fail | Safe Fail | Safe Fail |
Mechanical & Environmental | |
Operating Temperature Range | Ta | -40ºF to +158ºF [-40ºC to +70ºC] |
Permissible Operating Humidity | RH | 5%...95% |
Atmospheric pressure and altitude | 80k Pa ... 106k Pa / -500 m.....2000 m |
Terminal Screw Torque | Mmax | 39.9 Ibf ·in [4.5 Nm] |
Conductor Cross Section (max) | 2 AWG (Solid, Stranded) / 4 AWG (Flexible) |
| 35 mm2 (Solid, Stranded) / 25 mm2(Flexible) |
Mounting | 35 mm DIN Rail, EN 60715 |
Degree of Protection | IP 20 (built-in) |
Housing Material | Thermoplastic: Extinguishing Degree UL 94 V-0 |
Thermal Protection | Yes |
Operating State / Fault Indication | Green ok / Red defect |
Remote Contacts (RC) RC Switching Capacity RC Conductor Cross Section (max) | Optional AC: 250V / 0.5 A; DC: 250V / 0.1 A;125V / 0.2 A;75V / 0.5 A 16 AWG (Solid) / 1.5 mm2(Solid) |